Utilities Safety Branch

Natural Gas & Propane Safety Report For 1999

July 2000

CPUC Headquarters Los Angeles Office

505 Van Ness Avenue 320 West 4th Street, Suite 500

San Francisco, CA 94102 Los Angeles, CA 90013

Page No.

Memorandum......................................................................................... v

I. Introduction....................................................................................... 1

II. Utility Companies Under the Jurisdiction of the CPUC ..................... 33

Page No.

III. USB's Gas Statistics for 1999........................................................... 36

IV. Additional Information ................................................................... 41

Page No.

Table 1. Miles of Distribution Pipeline in California by Utility............................... 23

Figure 1. Chart Illustrating Amount of Pipe in California by Type............................ 23

Table 2. Miles of Transmission Pipeline in California by Utility............................ 24

Figure 2. Miles of Transmission Pipeline - 1999 ............................................... 24

Table 3. Number of Services in California by Utility in 1999 ............................. 25

Figure 3. Number of Services in California by Utility......................................... 25

Table 4. Number of Leaks Detected on Mains and Services in California in 1999 ....... 26

Figure 4. Total of All Leaks Repaired .......................................................... 27

Figure 5. PG&E - Leaks found on Mains ....................................................... 28

Figure 6. PG&E - Leaks found on Services ..................................................... 28

Figure 7. SCG - Leaks found on Mains ........................................................... 29

Figure 8. SCG - Leaks found on Services ....................................................... 29

Figure 9. SDG&E - Leaks found on Mains ...................................................... 30

Figure 10. SWG - Leaks found on Mains ........................................................ 30

Figure 11. Cause of Reportable Incidents......................................................... 31

Table 5. G.O. 112-E Inspection Person-days Conducted in 1999............................ 37

Table 6. Units Inspected and Probable Violations.............................................. 37

Table 7. Summary of Violations................................................................... 38

Page No

Table 8. Summary of Leaks Found in 1999...................................................... 38

Table 9. Incidents Reported and Investigated ...................................................39

This annual report of Natural Gas and Propane Safety presents an account of various activities carried out under the California Public Utilities Commission's (CPUC) natural gas and propane safety programs for the 1999 calendar year. The CPUC has been entrusted with safety jurisdiction over certain natural gas and propane facilities in the state by legislative mandate. It is responsible for enforcing safety regulations, inspecting all work affected by the statutes and making necessary additions and changes to regulations for promoting the safety of the general public and the utility employees that work on the system.

Regulations for the natural gas and propane safety programs are stated in General Order (G.O.) 112-E. G.O. 112-E adopts Title 49 of the Code of Federal Regulations (49 CFR), Parts 190-199 and Part 40 that pertain to natural gas and/or propane safety. G.O. 112-E also includes a few regulations, which are more stringent than the federal regulations. Other pertinent legislation is stated in the Public Utilities Code. The CPUC's Utilities Safety Branch (USB) oversees the safety programs and maintains an adequate level of inspections and surveillance to ensure that these systems are designed, constructed, operated, and maintained in accordance with the regulations for safety of the general public. It also conducts accident investigations, follow up investigations, compliance inspections, review of utilities' reports and records, construction inspections, and on occasion conducts special studies regarding pipeline safety.

Acknowledgment

This report was prepared by Grayson Grove, Senior Utilities Engineer for the Utilities Safety Branch of the Consumer Services Division under the general direction of Mahendra Jhala, Chief, and Julian Ajello, Program and Project Supervisor. The staff also acknowledges the assistance provided by the utilities and agencies in furnishing data necessary for this report and expresses its appreciation for their cooperation.

I. INTRODUCTION INTRODUCTION INMEMORANDUMM

A. PURPOSE OF REPORT

This Annual Report provides general information about the Utilities Safety Branch's (USB) activities and summarizes the progress of its safety programs during the 1999 calendar year. The California Public Utilities Commission (CPUC) monitors the pipeline safety of investor owned gas utilities, mobilehomeparks and certain propane systems under General Order (G.O.) 112-E. The Utilities Safety Branch (USB) is charged with enforcing G.O. 112-E, which adopts Title 49 of the Code of Federal Regulations (49 CFR), Sections 190, 191, 192, 193, and 199. The mission of the USB is to regulate pipeline safety of utilities under Commission jurisdiction and assure an acceptable level of operational safety for the protection of the public and the utilities' employees.

B. CPUC's RESPONSIBILITIES

1. G.O. 112-E

In 1995, the CPUC adopted the sections of 49 CFR that pertained to gas safety. By CPUC resolution the current version of 49 CFR was automatically incorporated into G.O. 112-E. The federal government's Department of Transportation (DOT) oversees the Office of Pipeline Safety (OPS), the Research and Special Programs Administration (RSPA) and the Transportation Safety Institute (TSI) which all play a role in modifying the regulations. Since the CPUC received federal grant money for carrying out gas safety programs and the CPUC required a resolution each time it changed G.O. 112-E to adopt any amendments, it made sense to adopt the federal regulations. G.O. 112-E presently retains some California regulations in addition to the federal regulations.

G.O. 112-E requires the USB to conduct audits of the regulated utilities' natural gas facilities and jurisdictional propane systems. The large utilities are made up of a number of operational units, such as divisions, each of which is normally audited every two years; half the divisions in one year and the other half in the next. When a significant problem is found, the inspection interval is reduced to either one year or six months depending on the severity of the problem. Once the problem is remedied the unit returns to the two-year inspection cycle.

During these audits, the USB inspectors (sometimes referred to as auditors) review the utilities' Emergency Plans and Operation and Maintenance (O&M) practices looking for deficiencies or oversights. USB staff reviews leak survey records to determine if the utility is meeting the appropriate standards for repairing leaks. They review the utility's cathodic protection records to assure that corrosion control is being maintained in accordance with the regulations. They insure that the utility is properly certifying its welders and pipe joiners. Finally, they check records pertaining to the anti-drug and alcohol program performed by the company.

The field inspection focuses on verifying the utility records by physically operating valves, checking regulator set points, randomly testing cathodic protection areas and verifying that repairs have actually been completed. Inspectors also observe the overall condition of the system and how the utility follows its published procedures. The USB inspectors will cite the utility for noncompliance and specify the time within which corrective action must be taken. The USB also suggests or implements programs to improve the utilities' performance regarding gas pipeline safety.

2. Description of a Typical G.O. 112-E Inspection

The inspector audits records and pertinent documents in the operator's office and then conducts a field audit to determine if the facilities are operating properly. In the operator's office, the auditor determines if the operator possesses a complete and accurate map of the gas or propane system, an Emergency plan and an adequate Operation and Maintenance (O&M) plan (with documentation that the plan is being followed). The auditor reviews the utility's records and verifies that the proper maintenance and appropriate surveys, such as cathodic protection, leak detection, odorant checks, were performed in accordance with state and federal regulations. The auditor frequently uses this review of the records as a guide to select the utility facilities to audit in the field.

During the field audit the inspector focuses on the condition and operation of the facilities. For the large utilities, this usually includes measuring the amount of cathodic protection on steel pipes, verifying the set points on overpressure protection devices, visually inspecting above ground facilities and exercising critical emergency valves to assure they can easily be found and operated. This inspection also may be used to verify the records that were reviewed in the operator's office.

The staff aids operators of small Mobilehome Parks (MHPs) and Propane Safety Program (PSP) systems. If an operator needs to prepare an O&M or emergency plan, the USB auditor helps him by answering questions and gives him a copy of our brief O&M and Emergency Plan guide. The auditor may be more of a teacher during the initial audits. For both systems, the auditor should conduct spot checks to assure the system is in compliance with the existing standards (i.e., this includes cathodic protection levels, general condition of the facilities, atmospheric corrosion and possible gas leaks). If a PSP operator has existing (permanent) bar holes, the auditor may randomly test them with a combustible gas indicator, commonly called a CGI (instrument that measures the amount of a combustible gas in an air sample usually drawn from a bar hole with a long narrow probe). Otherwise, he/she will do a random above ground survey, concentrating on meter and tank connections as well as low lying areas where propane may collect.

Without naming specific firms, the safety inspector can suggest that the operator obtain the services of a consultant for performing leak surveys, cathodic protection, and if necessary, repair. A consultant could also prepare an O&M/Emergency Plan. The inspector should inform the operator of possible options he may consider as well as possible pitfalls in pursuing any course of action. The inspector is directed to just state facts and try to be helpful without recommending any specific type of action, brand names or specific consultants. Our goal is to establish a reasonable inspection that will ensure the propane system is safe and the operator is following good maintenance procedures to minimize the occurrence of accidents.

3. Mobilehome Park (MHP) Program

The majority of natural gas customers in California receives gas directly from and is billed by the local gas utility. Some customers in California do not receive gas directly from the local utility. They receive gas from and are billed by the mobilehomepark operator. In this case, the park is operating a master meter system. The park receives this gas at a slight discount since the local utility is not responsible for maintaining and operating the park's natural gas distribution system. The park, in turn, bills its residents at the rates that are prescribed in CPUC's tariffs for the serving utility.

The difference between what the master meter operator pays for gas from the utility and what the operator charges its residents is not all profit. Instead, these funds are to be used by the master meter operator to maintain and operate a safe natural gas system within the park. Any money left over becomes profit for the operator. Some operators do not adequately maintain their systems, even though they are obligated to conform to the same rules concerning maintenance and operation as are followed by the natural gas utilities.

The MHP program provides for periodic inspections of mobilehomepark operators who have master metered systems. These operators are expected to meet the requirements outlined in the federal "Guidance Manual for Operators of Small Gas Systems". USB inspectors are charged with carrying out this program and have the authority to cite operators who are in noncompliance with the law. In addition to inspections, the USB offers training seminars to master meter operators to reacquaint seasoned operators and introduce new operators to the requirements for operating a gas system.

USB's MHP Program was implemented in 1991 and is funded partially by the federal government with the remainder funded by a user fee of approximately 20¢ per month per space, which is collected by the utility. This fee fluctuates annually depending on the actual cost of the program and the amount of federal funding. If the fee does not change, no resolution is required as the old resolution provides for a continuation of the fee. Commission Resolution G- 3281, dated June 8, 2000, set this fee at 21¢ per month per space for the year beginning July 1, 2000. USB is responsible for inspecting just about 2800 master meter mobilehomeparks in California ranging in size from 2 to over 1,000 customers at least once every five-years. Many of the parks require special attention to meet state requirements. This requires USB to conduct follow-up inspections of certain operators more than once during the five-year period.

The program has been successful. Many potentially dangerous situations have been found by USB inspectors and corrected before an incident occurred. USB logs the results of the inspections in a database and tracks the annual reports. It also follows up to assure operators who have been cited make the appropriate repairs to their systems. The database is also used to identify problem areas, which need to be addressed.

4. Propane Safety Program (PSP)

The Propane Safety Program (PSP) is modeled after the MHP program. The same "Guidance Manual for Operators of Small Gas Systems" is used. DOT is preparing a version specifically for propane operators. Operators are required to have a map of their system, an emergency plan, and an operation and maintenance plan to assure safe operation of their systems. USB inspectors verify that the propane system operator knows the requirements of the code and understands the operation and maintenance of the system. USB engineers also perform a visual inspection of the system to determine if any obvious problems exist.

The PSP was precipitated by a number of propane related incidents involving death and injury that occurred in the Sierras in 1992 and 1993. Investigation of these incidents revealed that operators of the propane systems had very little safety regulation. As a result, Assembly Bill (AB) 766 (Hauser) became law on September 1, 1994 and was later amended by AB 2430 on September 19, 1996. The Public Utilities (PU) Code incorporates the law in sections 4451 through 4465. This program directs operators of jurisdictional propane distribution systems in California to comply with the federal pipeline safety standards, and permits the CPUC to adopt rules, at least as stringent as the federal law, to protect the health and safety of the operators, their employees and the customers they serve. The CPUC's responsibility covers all propane distribution systems serving 10 or more customers in a residential or commercial district, and 2 or more customers located in a mobilehomepark.

Under existing law, the operator is subject to an inspection every two years for those systems that serve over 200 customers. USB audits systems that serve at least 100 but less than 200 customers every three years. Approximately 95% of the propane systems serve less than 100 customers and are audited at least once every five years. USB is proposing legislation to change the inspection cycle to be based on need rather than size of the park, because many large systems are well maintained while some smaller systems need more frequent inspections. According to the law, operators may be cited and fined if corrective action is not taken in a reasonable period of time for any noncompliance found during the audit.

The jurisdictional propane systems were identified by using existing databases, conducting phone surveys and making field verifications during the early years of the program. Approximately 750 jurisdictional systems were identified. Of these, approximately 231 were fully audited by USB inspectors since 1997 and 50 were determined to be non-jurisdictional. As with any new program, USB's inspectors are finding that many operators, who are not suppliers, have little knowledge of their system. In these cases, the inspector becomes an instructor, working with the operator to list necessary actions to increase safety and bring the distribution system into compliance with federal regulations. The operator is then given a date by which to comply. Penalties for non-compliance are outlined in the PU Code. Our inspectors are finding that many operators are hiring consultants to inspect and leak survey their systems prior to our inspections. These operators are striving to comply with the law and as a result the propane systems in California are becoming safer.

USB works with the propane industry, mainly through the Western Propane Gas Association (WPGA) to improve the program. Many of the operators of these propane systems also supply the propane. They are usually knowledgeable about the system, safety, and the federal regulations. USB listens to the concerns of these operators, and will seek necessary legislation to improve the program, if warranted.

Based on its early experience with this program, USB is working at solving several problems. The first problem is capturing all jurisdictional systems in the database and keeping the database current (i.e., removing entities that become non-jurisdictional and adding new entities as they become jurisdictional). There is no existing reliable and comprehensive database of propane master tank operators that contains the information necessary to determine whether they are subject to Commission jurisdiction. Inspectors look for previously undiscovered jurisdictional installations during inspection trips. One obvious source of information to identify propane distribution systems is the propane suppliers who deliver gas to these systems. However, they are not required to provide USB any information and generally decline to do so voluntarily unless a customer has been taken away from them.

Second, trends have developed which point out common problems found during our inspections. Cathodic protection and record keeping are prime examples. USB is trying to educate not only the small operators, but many of the suppliers, to better understand how cathodic protection works and what they need to do in order to achieve compliance at minimal expense.

In addition to implementing the program, AB 2430 requires the CPUC to collect a user fee from the propane operators under its jurisdiction. At present, the fee is set at twenty-five cents per unit per month or $3.00 per unit per year. In accordance with the legislation enacted to implement this program, every operator of a propane system serving 10 or more units in a commercial or residential area or 2 or more mobile homes must prepare and submit to the CPUC a completed Annual Report form and pay the annual user fee.

Collecting the user fee is another problem due to the changes in park ownership, park operators, propane suppliers and maintenance staff. Program costs are estimated to be $300,000 to $360,000 to inspect approximately 750 jurisdictional operators serving 30,000 customers. Assuming all operators pay the user fee, this program could generate up to $90,000 annually. Unfortunately many operators are not paying the user fee, which results in less revenues and higher expenses (to collect from those who have not paid). Consequently, the revenue collected does not offset the cost of billing and collection. This is the only program for which USB is obligated to bill and collect a user fee.

5. Gas Incident Reports

The USB monitors and investigates gas incidents, which occur in the service territory of utilities under Commission jurisdiction. The purpose is twofold. First, to determine the cause and whether the utility was negligent or violated G.O. 112-E; and second, to determine if measures can be taken to prevent similar incidents. By keeping a log of the incidents, the staff can track any trends that are occurring in gas incidents and initiate action to prevent them. Tracking leak histories and incident occurrences have led to the "Pipeline Replacement Program", "Meter Protection Program" and the "Above Ground Pipeline Inspection Program".

Each utility is required to report any incident which involves death, injury, $50,000 or more of damage to property, including loss of gas, or in the operators judgment is significant, to the CPUC and United States Department of Transportation (DOT). These incidents are to be reported to both the CPUC and the DOT within 2 hours (during working hours) and 4 hours (during non- working hours) of the crew arriving on the scene. The USB has more stringent incident reporting requirements than the DOT. In addition to the requirements above, USB requires the utility to report any incident that involves significant media coverage. USB also requires the utility to file a quarterly report listing all reportable and non-reportable incidents that involve the escape of natural gas. This report includes all incidents from minor dig-ins to large incidents that involve fire or explosion, regardless of the amount of property damage. This data is tabulated, analyzed and used to evaluate the need to develop other programs or modify existing ones.

The USB staff investigates those incidents it believes are significant. This may be done by conducting a full scale investigation, visiting the site, making written data requests, conducting phone interviews with the operator and witnesses of the incident or a combination of these activities. The major cause of gas incidents is "Dig-ins" which account for more than half (57%) of the reportable gas incidents (approximately 90% of the non-reportable incidents). 25% is caused by "Outside Force" and 7% by vehicles damaging facilities. The remaining 11% is made up of incidents caused by corrosion, construction, and operator error (See Figure 11). Many incidents are caused by home owners and small contractors doing work on the customer's property which are not reportable because they do not meet the criteria established by the CPUC or DOT. Damage causing fire/explosion still accounts for approximately 10% of the total number of reportable incidents.

Some people equate the number of leak repairs to the number of incidents. This is not an accurate comparison. USB engineers audit the utilities' leak repair records, which include repairs of all leaks, including those caused by incidents. Many of these leaks are detected by leak surveys rather than incident reporting.

The statistics illustrate the following causes of leaks (See Figure 4):

Approximately 68% of all the leaks found in 1999 were repaired in that year. Most of those that were not repaired (32%) were considered to be minor and did not require immediate attention (grade two leaks which are to be monitored and were probably repaired in the following year if they were not downgraded).

On average, about 400 to 500 natural gas incidents are reported to the USB every year in the utility quarterly reports. Of these, 76 were reported to the USB as reportable in 1999. Only 9 were reported to DOT as reportable incidents. Some of the reportable incidents are questionable because they may involve considerable damage, death or injury while the cause is unknown. For example, a house fire started by faulty wiring, causes a wall to fall on the gas meter and it is not immediately obvious that the broken gas meter was not the initial cause of the fire. In order to comply with the state and federal rules, the utility tends to assume an incident to be CPUC or DOT reportable if gas could have been the cause and rescinds its notification if gas was found not to be the cause.

During the last three years many of the DOT reportable incidents involved damage over $50,000. There were very few fatalities or injuries related to natural gas incidents. Most of the reportable incidents that resulted in injury or fatality were caused by attempted suicides, leaks from faulty gas appliances within the home, or fire. Surprisingly, very few people were injured, as a result of a gas incident.

6. Safety Related Condition Reports

Safety-Re1ated Condition Reports are required by the DOT to monitor situations that could affect public safety if not repaired in a timely manner. These reports are generally required in the event of a natural disaster, physical damage (e.g., dig-in), corrosion, material defect or operating error causing the integrity of the pipe to be compromised and the pipe cannot be repaired within five days. It usually results in the utility reducing pressure or shutting down the line. The complete definition is found in 49 CFR, Parts 191.23 and 191.25. The utilities appear to dislike monitoring this type of condition and prefer to repair the occurrence as soon as possible. Most utilities prefer to handle it as if it were an incident and repair it in less than five days. As a result, California utilities file a minimum number of "safety-related condition reports" (1-5 per year) during the calendar year.

7. Drug and Alcohol Testing Program

Utility Drug Testing Programs were required by DOT in 1990. Alcohol testing was incorporated in 1995. Each utility is now required to have a drug and alcohol testing program that conforms to the guidelines set forth by DOT in 49 CFR, Parts 40 and 199. In essence, the utility is required to randomly test utility employees that perform "emergency response functions" in accordance with DOT's procedures. USB monitors the utility's performance by performing a thorough audit at the utility's headquarters of its Drug and Alcohol Plan. USB also audits the medical review officer (MRO), the collection process, drug testing laboratory and the chain of custody of the sample. The headquarters audit is supplemented by information gathered in periodic G.O. 112-E audits of the operator's field offices where questions are asked concerning the utility's Drug and Alcohol Program.

8. Underground Service Alert (USA)

USA was established to minimize the damage caused by dig-ins. USA is funded by its member utilities (gas, electric, water, telephone, cable, etc.) that are at risk of a dig-in. Each USA member pays dues based on either miles of facilities in the ground or population with some weight given to the importance of the buried facilities (e.g., a fiber optic cable or large high pressure gas line has more importance than a 2 inch water line). The function of USA is to provide a single 800 number for excavators to call (One call system) 48 hours before they dig. USA notifies utilities that have facilities in the area to locate and mark them so the excavator will be aware of their location prior to digging.

Calls made to the 800 number are directed to one of two USA organizations in California; one serving northern California and the other serving southern California. Approximately 600,000 calls are made annually to the two locations. Of these calls, less than one-half of one percent result in a contractor damaging a pipeline. Major contractors tend to call before they dig. Some small contractors and homeowners appear to be unaware of the need to call before they dig and therefore, learn by an unfortunate experience. Even though violators are subject to fines, they are rarely levied. The USB has endeavored to promote legislation to increase penalties for not calling USA, especially for repeat offenders. USB also sends warning letters in particularly egregious cases. Presently, the State Contractor's License Board will revoke contractor licenses if it is determined that the contractor is ignoring the rules. USB has recently created a "dig-in" database, which can be used to monitor the effectiveness of the program and determine what companies are repeat offenders.

9. Pipeline Replacement Program (PRP)

The PRP is of paramount importance to a gas utility. Its purpose is to replace old gas pipe, which is technologically obsolete and prone to leakage or failure, with new pipe. Pacific Gas and Electric Company (PG&E) and Southern California Gas Company (SCG) have implemented programs which evaluate the numerous factors that must be considered in determining the priority of replacement. In general, the type of pipe, age, condition, location, proximity of known faults, population density and leak history are the major considerations in setting the priority. As a result of the Loma Prieta earthquake in 1989, seismic effects were added as a major consideration in the formula. At this time, each pipeline segment has a seismic factor which is computed using four factors: (1) the probability of strong ground shaking, (2) the probability of surface faulting, (3) the susceptibility to soil liquefaction and (4) the susceptibility to slope failure or landslide.

PG&E and SCG presently use all these factors to develop a priority list for pipeline replacement. Both programs are well designed and appear to be an accurate method for planning and financing future replacements systematically. Each utility tracks the progress of its program detailing what has been accomplished and what remains to be completed. The priorities are subject to modification with substantial cause. For example, when a utility learns of a planned re-paving project, it may rearrange priorities so that scheduled pipe replacement can be accomplished just before the paving project. Working closely with local public works departments is appreciated because it reduces disruption of traffic. As a result some pipeline replacement projects may be accelerated and others de1ayed.

Cast iron pipe replacement has always been at or near the top of SCG and PG&E's priority lists. Southwest Gas Corporation (SWG) and San Diego Gas and Electric Company (SDG&E) do not have cast iron pipe in their systems. SCG recently finished replacing the cast iron pipe in its system. PG&E has approximately 300 miles of cast iron pipe (mainly in the San Francisco Bay area) left to replace (as shown by Figure 3). PG&E is systematically replacing these pipes as well as other high priority pipe. PG&E projects that it will complete its cast iron replacement in approximately six years.

Pre-1931 steel distribution mains and steel transmission lines with joint configurations and girth welds not meeting current standards are a high priority on all utility pipe1ine replacement programs. These pipelines may be higher priority for replacement than cast iron if they operate at higher pressures, are located in highly corrosive areas, are subject to earth movement, are situated in a heavily populated area or have a leak history that logically places them at a greater risk of failure.

Leak surveys and evaluations regarding the cause of recently replaced pipe are used to judge the original pipeline replacement priorities. This coupled with unforeseen events, such as natural disasters, changes in operating conditions, city or county re-paving programs, load shifts and funding all have an impact on the original set of priorities. With proper cause, replacement priorities can and should be modified. USB monitors these modifications and determines if they are in the best interest of public safety.

10. Meter Protection Program

The meter protection program was initiated because statistics indicated numerous vehicles were hitting meters and rupturing gas pipelines. Upon further investigation of the statistics, it was determined that many of these incidents could have been avoided, if gas meters were either relocated or protected by steel posts. In the late 1980s, gas companies considered meter protection programs in order to minimize the vehicle-caused incidents that occurred in their service territory. In 1990, the Commission ordered gas companies to develop a meter protection program and provide the Commission with annual status reports in order to monitor the utilities' progress. Initially, meter readers were to identify those meters that they felt were vulnerable to being struck by a vehicle. These meters were evaluated by a utility expert and many were slated to be protected. As a direct result of this program, the number of incidents involving a vehicle has decrease substantially.

11. Pipe Lining Rather than Replacement

PG&E requested a waiver from the federal regulations to use a liner in an existing pipeline rather than replacing the pipe. The new technology was less expensive and less disruptive to traffic than excavating a street and replacing the pipeline. In 1995, PG&E installed this liner in a large main in the San Francisco area. The pipe liner appears to be a cost-effective solution to replacement for pipelines that are prone to leakage. USB is still monitoring the status of this new technology and how it performs over time. It is through the waiver process that new technologies are tested and if proven to be effective are incorporated into the regulations.

12. Granting Of Waivers

The process of granting waivers normally involves a regulated utility requesting to do something not covered by the existing regulations. In order to use a new product or technology the utility requests USB to evaluate the merit of the utility's proposal. If USB is convinced this request has merit, it will prepare a resolution for CPUC approval to grant a waiver contingent upon DOT/OPS approval. If the waiver is granted, the utility may proceed with the project for which the waiver was granted. It cannot use this technology elsewhere until DOT incorporates the new technology into the regulations or the utility requests and is granted a new waiver to use the technology in another project. A good example of how a request for a waiver eventually is incorporated into the regulations is SCG's persistent requests for waivers to install larger diameter polyethylene pipe than allowed by the regulations on various jobs. SCG was convinced that the pipe was safe and economical to use in their system. Eventually the regulations were changed to allow this pipe to be installed. During 1999 no waiver requests were made by the utilities.

13. Above Ground Pipe Inspections

Above ground pipeline inspections were initiated in 1990 after significant corrosion was observed on a major transmission line. Inspections revealed big differences in the surface condition of exposed piping in different districts within the same utility. In some districts above ground pipe was in excellent condition while in an adjacent district, there were frequent instances of surface rust and pitting.

As a result of these inspections, USB is directing some of the utilities to identify all above ground spans, state the general condition of each span, confirm when it was last inspected, identify who conducted the inspection, and indicate when the work will be completed on the span, if needed. When this procedure is refined, USB will implement the program statewide. All utilities will be required to keep records of above ground facilities and these records will be reviewed during the course of normal G.O. 112-E inspections.

14. Seismic Safety Program

As a result of the Loma Prieta earthquake the Seismic Safety Commission (SSC), which is charged with implementing an earthquake hazards reduction program for the state, set milestones for identifying and mitigating earthquake hazards. The CPUC was designated as the lead agency for utility systems providing critical services. In the process, the SSC set forth the following milestones:

A. Establish, by August 1, 1989, the channels of communications to all parties which have an interest in this sector.

B. Establish, by January 1, 1990, appropriate seismic safety criteria and procedures for design, construction and operation of new facilities, hazard mitigation, and reliability improvement for existing facilities.

C. Establish, by July 1, 1990, suitable emergency response criteria and procedures to assure rapid restoration of services and to facilities repair or replacement of damaged or destroyed systems.

D. Determine, by January 1, 1991 if existing state authority is adequate to assure that seismic safety criteria and procedures will be met.

E. Provide, by July 1, 1991, for any additional state authority required to establish all seismic safety criteria and procedures.

USB staff met with the SSC after the Loma Prieta earthquake to share information of the progress being made to restore service and to discuss earthquake preparedness. In light of the significant amount of information gathered from the earthquake, the USB requested, and was granted, an extension of time from the SSC to respond to the milestones previously established by the SSC. The SSC agreed to accept a report from the Commission which would address the following five elements:

1. Policy Statement: A statement of policy that states goals, expectations, and deadlines, and explains the ranking of seismic safety in the agency's responsibilities.

2. Seismic Safety Program: A seismic safety program with a plan and process to identify earthquake hazards to people and to the organization's functions, to abate the unacceptable hazards, and to prudently manage the risks that cannot be eliminated.

3. Responsible Staff: A management 1evel agency official having clear responsibility for meeting the goals in the policy statement, and an appropriately sized staff that has the administrative and technical knowledge and experience needed to carry out the program.

4. Adequate Funds: Funds adequate to carry out the program or a plan to raise the funds needed.

5. Accountability: A way to measure and report progress to the person or organization legally responsible for the agency, and to the Governor and the Legislature, and a way to ensure technical performance in carrying out the program.

Since 1990, the USB has worked with the utilities to insure that the above-mentioned five elements provided the foundation for the utilities' responses, and to determine various seismic considerations, parameters and lessons learned from the Loma Prieta (1989), Northridge (1994) and other earthquakes. It should be noted that many of the preventative measures suggested in this report are currently being considered or have been implemented by the utilities. Further, all utilities were found to be well aware of seismic issues. Damage caused by both the Loma Prieta and the Northridge earthquakes indicates that gas systems survive with relatively minor damage compared with other types of structures in the area of seismic activity. The USB is of the opinion that the major utilities have each deve1oped a comprehensive and effective seismic safety program.

15. Other Programs

USB is currently looking at new technology and pragmatic solutions to handle the current concerns in this state to improve gas safety. Paramount on this list is to improve on the existing method to control gas during and immediately after a seismic occurrence. If the interior house/building gas lines are damaged and leaking, it might be useful to have a device that would automatically shut off the gas at the meter. The city of Los Angeles adopted rules to mandate installation of these valves under certain conditions and SCG conducted a pilot program to install these devices. Numerous valves have been installed in southern California at customer expense. False closures of these valves may be a problem. Other firms are working on a product that would sense the presence of gas in the air. The sensor would detect the amount of methane (CH4) in the environment and possibly carbon monoxide (CO), and at preset 1eve1s would shut off the gas supply to the building. The device would also sound an alarm much like a smoke detector notifying the occupants with two alarms: first, that there is a problem and the gas is about to be shut off and second, when the gas is automatically shut off. It is expected that most of the existing seismic shut-off valves will have some problems. USB believes the real test will come when there is a seismic event that triggers these valves.

The USB is also looking at better ways to measure the condition of pipelines. Manufacturers are currently developing devices that can be inserted into a gas line, travel through it and locate any areas of corrosion or damage. These devices are called "smart pigs". In time, they will be able to provide video of the interior of the pipe, measure wall thickness, determine where the pipe wrap may have been damaged, positively locate the area of concern and in some cases even repair certain conditions. These smart pigs combined with the improvement of other gas detection devices will improve the safety of the gas systems.

Other devices such as pipe liners capable of being inserted into existing pipes may greatly reduce the cost of pipeline replacement especially in highly populated areas. System Control And Data Acquisition (SCADA) systems are being used to remotely monitor critical pipeline facilities and in some cases, work as an early warning system to alert the utility to a potential problem such as overpressurization. Programs continue to be enacted as a result of information gathered following a natural disaster (e.g., the water heater strapping program resulted from investigations of the causes of natural gas fires following an earthquake).

16. Other Duties Required by the Pipeline Safety Act

The USB is required to log each of the regulated utilities' major construction projects, uprates and hydro tests. During the process of recording the construction projects, USB staff also checks the utility's calculations to verify the pipe has adequate wall thickness to carry the pressure. In addition, USB reviews the type of project (new or replacement), the location of the project, and the pipe material being used. It also performs random inspections of these activities. These inspections are usually conducted when time permits or a significant job warrants an inspection.

The USB is annually audited by the DOT to verify its ability to perform as an agent for the federal government. Federal funding is based on the results of this audit. The audit consists of reviewing USB's records of the previous year. Records regarding incident reports, inspections, citations for noncompliance and knowledge of the federal law are reviewed. Person-days spent on auditing utilities and investigating gas incidents are weighted heavily. DOT also accompanies staff inspectors when they perform an audit of the utility. The DOT also requires the USB to account for its actions, to have its inspectors fully trained by attending all the required courses at DOT's Transportation Safety Institute (TSI), to implement new rule changes in the federal regulations and to participate in certain annual meetings.

It is expected that a number of new provisions will be looked at during the next few years. Many of these concerns will deal with pipeline safety and effect on the environment. The Pipeline Safety Act of 1992 places the environment on an equal basis with safety in making regulatory decisions. It appears DOT's Office of Pipeline Safety (OPS) is moving ahead with its risk-based planning approach. In its "work redesign" program, it identified the need for better analytical tools to assess the safety and environmental risks of pipe1ine transportation for long-range planning of activities. OPS is in the process of prioritizing the pipeline risks according to their probability of occurrence and consequences. In proposing solutions, it will consider the finite resources available and the relative costs and benefits to develop programs to address the risks. OPS intends to work with the industry, states and general public during this process.

OPS and DOT's Research and Special Programs Administration (RSPA) has added Subpart N (192.801 to 192.809) to the Federal Regulations which requires operators of gas systems to have a written "operator qualification program" by April 27, 2001. The operator is required to keep records including the name of the individual, the covered tasks the individual is qualified to perform, the method(s) used to qualify the individual and the date(s) of qualification. These records are to be kept for a minimum of five years under federal requirements. USB in cooperation with OPS/RSPA and TSI is developing guidelines to evaluate the operator's compliance with the new regulations.

C. SIGNIFICANT RULEMAKING AND DECISIONS

1. Utility Responsibility Regarding the Installation of Seismic Shut-off Valves

The Commission issued Decision 00-06-038 in response to an application filed in the spring of 1999 stating that the utility is responsible for ensuring the safety of earthquake valves (EQV) installed on its side of the gas meter. This utility allowed independent contractors to install EQVs on the utility's side of the meter. Part 192 of the federal code requires utilities to be responsible for the integrity of the pipeline and all equipment placed on the pipeline upstream of the customer's piping. In California, that is normally at the outlet of the meter. In the case of remote meters, this requirement covers the pipeline to where it enters the building. This decision upholds state and federal law, which basically states that the utility is ultimately responsible for the integrity of the pipeline until it connects to the customer's piping regardless of who does the work. This decision allows the utility to submit an application to recover reasonable costs of inspecting EQV installations.

2. Utility Responsibility Regarding Termination of Service for Fumigation

The Commission issued Resolution G-3256 on January 6, 2000, stating that the utility would be responsible for terminating service to a building prior to fumigation. Prior to the complaint that was filed with the Commission, fumigation contractors were allowed to turn off the gas to the building. The tariff revision to Gas Rule 11 was prompted by three gas explosions in residences related to inadequate fumigation service termination policies. The rule established procedures for the fumigation contractor and the utility. The contractor must follow guidelines to notify the utility. If this is done, there is no fee charged by the utility for performing the service. There are penalties prescribed to ensure the contractor follows the guidelines. The utility must react and terminate service on the date requested. The resolution does not address any changes in Gas Rule 11 regarding the restoration of service.

D. SIZE OF THE CALIFORNIA GAS SYSTEM

The California gas system (gas and propane) serves approximately 8 million gas customers with 90,000 miles of gas mains. Six gas companies serve California's customers. Table 1 and Figure 1 illustrate the miles and type of distribution pipeline and Table 2 and Figure 2 indicate the miles and type of transmission pipeline in California in 1999. Table 3 and Figure 3 show the number and type of services each company had in 1999. Table 4 lists the cause of leaks determined by each utility on their system in 1999. Table 4 also shows the number of those leaks that were "not repaired " (minor leaks that are not required to be repaired immediately: many Grade 2 leaks could be scheduled to be repaired in year 2000). Figure 4 illustrates an overview of the cause of leaks in 1999 while Figure 5 through Figure 10 show the causes by utility for both mains and services. Figure 11 illustrates the cause of "reportable" incidents that occurred in California in 1999 and the text shows the difference between reportable and non-reportable incidents.

PG&E and SCG are two of the largest gas companies in the United States and serve most of northern (PG&E) and southern California (SCG). SDG&E, while a large company in its own right, is significantly smaller and serves the greater San Diego area. Southwest Gas Corporation (SWG) is smaller and serves approximately 110,000 customers in north Lake Tahoe and the high desert area near Victorville. Avista (formerly Washington Water Power Company, CP National and California Pacific Utility Company) is very small in California and serves south Lake Tahoe. Southern California Edison (SCE), one of the largest electric companies in the United States operates a very small gas operation that serves the town of Avalon on Catalina Island. It also operates a gas transmission line in the Los Angeles area to serve one of its generating stations.

Small companies, such as Alpine Natural Gas, are building systems to serve customers who were previously served by propane. Evidently, these companies believe that they can build a system, purchase gas from an existing utility, deliver it and make a profit. Even though the systems are small the operators of these systems will fall under CPUC jurisdiction and will be required to follow state and federal regulations. In many ways these systems are similar to the MHP operators. It is interesting to note the utility in the franchised area chose not to extend its system to serve these customers. USB will be watching to ensure that safety is not compromised in order to keep the systems viable.

While California produces some gas, most of the gas that is consumed in California originates in Texas, New Mexico the Rocky Mountain Overthrust (Wyoming) and Canada. The gas pipelines serving California are capable of delivering up to 7 or 8 billion cubic feet (Bcf) per day if each were running full and the demand existed. California underground storage fields are capable of holding over 200 Bcf of natural gas. Of the eight storage fields in California, two are large (over 50 Bcf), three medium sized (10-50 Bcf) and the remainder could be considered small (under 10 Bcf). All are strategically located to aid gas flows in event of a curtailment on a major transmission line or during severe demand during the winter.

Independent firms are developing underground storage to serve California utilities. Wild Goose Storage Inc., and Lodi Underground Storage are two operations that are under the Commission's jurisdiction for safety regulation. USB will inspect and monitor their operations. Both of these firms will be requiring reservation and variable charges from those wishing to use their service. Again, USB will be concerned about these operators compromising safety for any reason.

Table 1

Miles of Distribution Pipeline in California by Utility

Company

Steel Pipe

Plastic

Cast Iron

Ductile Iron

Copper

Other

Total

 

Unprotected

Protected

           
 

Bare

Coated

Bare

Coated

           

PG&E

465

-

-

20,901

15,738

383

-

-

-

37,487

SCG

5,302

5,567

76

15,504

17,077

-

-

-

-

43,526

SDG&E

-

-

-

3,691

3,286

-

-

-

-

6,977

SWG

-

-

-

451

1,779

-

-

-

-

2,230

AVISTA

-

-

-

124

108

-

-

-

-

232

Total

5,767

5,567

76

40,671

37,988

383

-

-

-

90,452

                     

. Figure 1

Table 2

Miles of Transmission Pipeline in California by Utility

                     

Company

Steel Pipe

Plastic

Cast Iron

Ductile Iron

Copper

Other

Total

 

Unprotected

Protected

           
 

Bare

Coated

Bare

Coated

           

PG&E

-

-

18

6,759

-

-

-

-

-

6,777

SCG

67

-

261

3,660

-

-

-

-

-

3,988

SDG&E

-

-

-

166

-

-

-

-

-

166

SWG

-

-

-

74

-

-

-

-

-

74

AVISTA

-

-

-

-

-

-

-

-

-

-

Total

67

-

279

10,659

-

-

-

-

-

11,005

                     

Table 3

Number of Services in California by Utility in 1999

                   
                   

Company

Steel Pipe

Plastic

Iron

Copper

Other

Total

 

Unprotected

Protected

         
 

Bare

Coated

Bare

Coated

         

PG&E

52,081

-

-

1,224,928

1,590,430

-

84,677

-

2,952,116

SCG

99,737

85,489

6,927

1,562,231

2,042,156

-

6,002

-

3,802,542

SDG&E

-

-

-

270,302

268,525

-

-

-

538,827

SWG

-

-

-

6,820

108,106

-

-

-

114,926

AVISTA

-

-

-

7,864

7,628

-

-

-

15,492

Total

 

85,489

6,927

3,072,145

4,016,845

-

90,679

-

7,423,903

Figure 3

Table 4

Number of leaks Detected on Mains and Services for the Major Gas Utilities in California

PG&E

Corrosion

Third Party

Outside Force

Construction

Material

Other

Total

       

Defect

Defect

   

Mains

365

615

36

272

133

371

1,792

Services

1187

1864

150

882

577

930

5,590

SubTotal

           

7,382

Not Repaired

           

3,741

               
               

SCG

Corrosion

Third Party

Outside Force

Construction

Material

Other

Total

       

Defect

Defect

   

Mains

1808

718

66

189

112

869

3,762

Services

2440

4109

151

254

150

1784

8,888

SubTotal

           

12,650

Not Repaired

           

3,629

               
               

SDG&E

Corrosion

Third Party

Outside Force

Construction

Material

Other

Total

       

Defect

Defect

   

Mains

35

160

52

73

21

124

465

Services

365

504

155

104

74

197

1,399

SubTotal

           

1,864

Not Repaired

           

40

               
               

SWG

Corrosion

Third Party

Outside Force

Construction

Material

Other

Total

       

Defect

Defect

   

Mains

1

40

7

51

0

5

104

Services

13

185

31

137

0

11

377

SubTotal

           

481

Not Repaired

           

5

               
               

AVISTA

Corrosion

Third Party

Outside Force

Construction

Material

Other

Total

       

Defect

Defect

   

Mains

2

105

1

7

9

7

131

Services

4

382

0

21

11

8

426

SubTotal

           

557

Not Repaired

           

0

Figure 4 illustrates a composite of all the leaks reported by the regulated utilities under CPUC jurisdiction. Figures 5 through 10 show a breakdown of these leaks as they are reported by utility for mains and services.

Figure 4

Figure 5

Figure 6

Figure 7

Figure 8

Figure 9

Figure 10

Figure 11

The CPUC has been granted authority by the Legislature to adopt and enforce requirements of G.O. 112-E on publicly owned utilities. There are six publicly owned natural gas utility companies within the state and three owned by municipalities with districts formed under the provisions of various laws of the State of California.

A. NATURAL GAS COMPANIES

1. Southern California Gas Company

Southern California Gas Company serves almost 4 million customers in southern California. Prior to the unbundling of its gas facilities it was capable of storing over 110 Bcf of natural gas in its 5 underground storage fields which could deliver over one Bcf per day to the system upon demand.

1.

2. Pacific Gas and Electric Company

Pacific Gas and Electric provides gas service to about 3 million customers. Its service area spans 70,000 square miles, including all or portions of 48 of California's 58 counties. Prior to unbundling PG&E had approximately 100 Bcf of underground storage capacity.

3. San Diego Gas and Electric Company

San Diego Gas and Electric operates under its parent company Sempra Energy and provides natural gas service to approximately 520,000 customers in San Diego and Orange county.

4. Southwest Gas Corporation

Southwest Gas provides natural gas service to approximately 110,000 customers in Victorville, Big Bear and North Lake Tahoe within California. The company also serves much of

Nevada and Arizona.

5. Avista Corp. (formerly Washington Water Power Co.)

This company serves approximately 15,000 customers at south end of Lake Tahoe.

6. Southern California Edison Company

Edison operates a gas system (propane /butane air) system on Catalina Island that serves approximately 1,000 customers. It also transports gas to one of its power plants. SCE is one of the nations' largest electric utilities, serving more than 11 million customers in a 50,000-square-mile area within Central and Southern California.

7. Municipalities

These California municipalities provide natural gas service to their customers.

· Palo Alto · Coalinga

· Long Beach

B. MOBILEHOME PARK (MHP) PROGRAM

The Utilities Safety Branch inspects approximately 2,800 mobilehome parks over a five year period (560 parks per year plus any re-inspections).

C. JURISDICTIONAL PROPANE SYSTEMS

USB inspects approximately 700 jurisdictional propane systems under CPUC regulation at least once every five years or over 140 systems per year plus any re-inspections. Larger systems must be inspected every 2 or 3 years depending on their size.

A. G.O. 112-E Inspection Areas

In 1999, USB personnel were divided into four units where each unit was assigned specific counties to conduct G.O. 112-E inspections in California. The following lists the counties each unit covered.

North : Alameda, Butte, Colusa, Contra Costa, Del Norte, Glenn, Humboldt, Lake, Marin, Mendocino, Modoc, Napa, San Francisco, San Mateo, Shasta, Siskiyou, Solano, Sonoma, Sutter, Tehama, Trinity, Yolo and Yuba.

Central: Fresno, Inyo, Kern, Kings, Madera, Mariposa, Merced, Monterey, Sacramento, San Benito, San Luis Obispo, San Joaquin, Santa Barbara, Santa Clara, Santa Cruz, Stanislaus, Tuolumne and Tulare.

Southern: Imperial, Los Angeles, Orange, Riverside, San Bernardino, San Diego and Ventura

Central Sierra: Alpine, Amador, Calaveras, El Dorado, Lassen, Mono, Nevada, Placer, Plumas and Sierra.

A file is kept on each area inspected for a period of at least 3 years. Every unit of a major gas company and municipal utility is inspected every two years or more often if the condition of the unit is unsatisfactory and not in compliance with federal law. MHP and propane systems are inspected once every 5 years unless the audit warrants more frequent inspection. Records are kept in both Los Angeles and San Francisco. The federal government audits USB's records annually. Federal funding to the state is based on these results. During the last three years USB has been receiving full funding (over $1 million per year) as a result of its performance based on the federal audit. The federal government divides the total amount allocated to gas safety by Congress and distributes the amount based on cost of each state's gas safety program and score received on the annual audit. It typically is less (40-45%) than the 50% funding requested.

B. USB Inspection Data

1. Inspections

For the 1999 Calendar Year

Total

Number of Person-Days of Utility Inspections

362

Number of Person-Days of MHP Inspections

412

Number of Person-Days of Propane Inspections

151

Number of Person-Days Inspecting Incidents

138

Number of Person Days Performing Other Field Work

70

Table 5. Summary of the G.O.112-E Inspection Person-days Conducted in 1999

2. Units Inspected and Probable Violations

For the 1999 Calendar Year

Total

Number of Inspection Units Inspected (Major utilities)

87

Number of Inspection Units Inspected (Municipal utilities)

2

Number of Inspection Units Inspected (Master Meter - Gas)

622

Number of Inspection Units Inspected (Master Meter - LPG)

85

Number of Inspection Units Inspected (Major Util.-Transmission)

74

Number of Inspection Violations Found

2,292

Number of Inspection Violations Corrected

1,567

Number of Compliance Actions Taken

617

Table 6. Tabulation of Inspections Conducted and Probable Violations Found in 1999

3. Summary of Violations

Utility

1998 Units Inspected

1999 Units Inspected

Total Units Inspected

Violations 1998

Violations 1999

Violations Total

PG&E

24

27

51

216

201

417

SCG

125

125

125*

70

91

161

SDG&E

11

0

11

10

0

10

SWG

1

3

4

8

1

9

AVISTA

1

0

1

5

0

5

TOTAL

162

155

192

309

293

602

*All of SCG's units are inspected annually

Table 7. Tabulation of Utility Inspections Conducted and Probable Violations

Found in 1999

4. Summary of Leaks Found in 1999

For the 1999 Calendar Year

Total*

Dig in

8,682

Corrosion

6,220

Material Defect

1,087

Construction Defect

1,990

Outside force

649

Miscellaneous other causes

4,306

Grand Total

22,934

Table 8. Summary of Leading Causes of 1999 Leaks Relating to G.O. 112-E

* (includes reportable and non-reportable)

5. Incidents Reported and Investigated

For the 1999 Calendar Year

Total

Number of Incidents Reported

77

Number of Incidents Investigated

77

Number of Gas Complaints/Inquiries Received

285

Number of Weeks for On Call Engineer Duties

52

Number of USB Engineers (person-years excluding managers)

8

Table 9. Summary of Incident Investigations & Customer Complaints

Handled by USB in 1999

C. GAS INCIDENTS & CUSTOMER COMPLAINTS

The USB staff receives and investigates reportable gas and propane incidents from regulated utility companies and from propane and MHP). G.O. 112-E states reportable incidents are those which involve the release of gas and: (a) result in fatality or personal injury rising to the level of in-patient hospitalization and attributable or allegedly attributable to utility owned facilities; (b) cause over $50,000 in damage including the loss of gas; and (c) are the subject of significant public attention or media coverage and are attributable or allegedly attributable to utility facilities.

The gas utility companies are required to provide notice to designated USB staff within 2 hours of a reportable incident. The notice shall identify the time and date of the incident, the time and date of notice to the Commission, the location of the incident, casualties which resulted from the incident, identification of casualties and property damage, and the name and telephone number of a utility contact person.

The designated USB staff is called the On-Call Engineer (OCE). The OCE is responsible for receiving reportable incidents from the utility companies and he or she is available 24 hours per day. The OCE duties are shared amongst the USB staff. Each staff engineer assumes the OCE duties for an entire week (including weekends) several times per year. The OCE or a staff engineer may investigate incidents at any hour, including weekends. If it is determined that a G.O. violation was involved, staff writes up a report and recommends action against the utility.

In addition, the staff maintains a database of outages and accidents to note trends. If there is significant trending, the staff will investigate and work with utilities to correct the problem. The database can be very useful in noting trends about dig-ins by excavators, manufacturer defects, corrosion areas, and need for meter protection. The Commission has initiated Orders Instituting Investigation (OIIs) based on the supporting data and investigations of USB. USB staff also may investigate customer complaints involving alleged violations of the General Orders, sometimes on behalf of Consumers Affairs Branch or through direct referral.

IV. ADDITIONAL INFORMATION CONTENTS

A. PUBLICATIONS

Copies of G.O. 112-E are available to the general public from the CPUC. Copies of federal regulations regarding pipeline safety must be obtained from the federal government. A form to obtain this information is on the last page of G.O.-112-E.

1. How to Order G.O. 112-E by Phone or Mail

Call or write to : Documents, California Public Utilities Commission

(415) 703-1713

2. How to Order G.O. 112-E and Federal Regulations Internet

· Can be viewed on the internet at http://www.cpuc.ca.gov (click on regulations).

· Federal Regulations can be viewed on the internet at http://ops.dot.gov/regsindex.htm

Top Of Page