IV. VIOLATIONS OF GENERAL ORDER 128

During the past three years (1998 through 2000), CSD staff found 677 violations of GO128 requirements in 791 SCE underground and pad-mounted structures.

The following table summarizes CSD's findings:

Year

Structures Inspected

GO128 Violations Found

GO128 Violations per Structure Inspected

1998

330

309

0.94

1999

237

184

0.78

2000

224

184

0.82

Total

791

677

0.86

The majority of the GO 128 violations fall into the following categories:

_ Equipment Oil: Violations related to equipment oil such as low oil levels and leaking oil from equipment (Rule 12.2).

_ Corrosion: Violations related to equipment corrosion (Rule 12.2).

_ Warning Signs: Violations of GO128 warning sign requirements (Rule 35.3).

_ Covers: Violations of GO128 requirements related to manhole and handhole covers such as securing and ownership identification (Rules 17.8 and 32.7).

_ Securing Structures: Violations of GO128 requirements related to securing pad-mounted equipment (Rule 34.3A).

_ Guarding Live Parts: Violations of GO128 requirements related to guarding exposed live parts in pad-mounted equipment (Rule 34.3B).

_ Structure Conditions/Locations: Violations related to the accessibility of pad-mounted structures for safe operation and maintenance (Rule 34.2).

Violations from the first four categories listed above were involved in at least one accident in the past three years.

Previous PageTop Of PageNext PageGo To First Page