During the past three years (1998 through 2000), CSD staff found 677 violations of GO128 requirements in 791 SCE underground and pad-mounted structures.
The following table summarizes CSD's findings:
Year |
Structures Inspected |
GO128 Violations Found |
GO128 Violations per Structure Inspected |
1998 |
330 |
309 |
0.94 |
1999 |
237 |
184 |
0.78 |
2000 |
224 |
184 |
0.82 |
Total |
791 |
677 |
0.86 |
The majority of the GO 128 violations fall into the following categories:
_ Equipment Oil: Violations related to equipment oil such as low oil levels and leaking oil from equipment (Rule 12.2).
_ Corrosion: Violations related to equipment corrosion (Rule 12.2).
_ Warning Signs: Violations of GO128 warning sign requirements (Rule 35.3).
_ Covers: Violations of GO128 requirements related to manhole and handhole covers such as securing and ownership identification (Rules 17.8 and 32.7).
_ Securing Structures: Violations of GO128 requirements related to securing pad-mounted equipment (Rule 34.3A).
_ Guarding Live Parts: Violations of GO128 requirements related to guarding exposed live parts in pad-mounted equipment (Rule 34.3B).
_ Structure Conditions/Locations: Violations related to the accessibility of pad-mounted structures for safe operation and maintenance (Rule 34.2).
Violations from the first four categories listed above were involved in at least one accident in the past three years.