Voltage at Point of Common Coupling

Maximum Trip Time

(Assuming 60 Cycles per Second)

Less than 60 Volts

10 Cycles

Greater than 60 volts but less than 106 volts

120 Cycles

Greater than 106 volts but less than 132 volts

Normal Operation

Greater than 132 volts but less than 165 volts

120 Cycles (30 cycles for facilities greater than 11kVA)

Greater than 165 volts

6 Cycles

*"Trip time" refers to the time between the abnormal condition being applied and the Distributed Generator unit ceasing to energize the Distribution System. Certain circuits will actually remain connected to the Distribution System to allow sensing of electrical conditions for use by the "reconnect" feature. The purpose of the allowed time delay is to ride through short-term disturbances to avoid excessive nuisance tripping. For systems of 11 kVA peak capacity or less, the above set points are to be non-user adjustable. For Distributed Generator units larger than 11 kVA, different voltage set points and trip times from those in Table 4.1 may be negotiated with the interconnecting Electrical Corporation.